SA82AR - SURGEX SA-82-AR 3 OUTLET POWER CONDITIONER AND SURGE PROTECTOR, IP ENABLED

SurgeX	SA-82-AR  3 Outlet Power Conditioner and Surge Protector, IP Enabled

The SurgeX® SA-82-AR is a network attached, IP addressed, web controlled AC surge protector and power conditioner. The SA-82-AR may be used to switch up to 8A at 120V. The simple web server structure allows basic control of two outlets. The extensive programming and setup capabilities are accessed by a web browser, through a Device Management Utility (DMU), or through a Command Line Interface (CLI).

  • The SA-82-AR features SurgeX® Series Mode® surge protection, Impedance Tolerant EMI/RFI filtering and Over-Voltage Shutdown.
  •  Remote reboot any device: monitors, routers, servers, kiosks, etc. The remote device need not be network attached.
  • Conserve energy by powering down equipment when not in use.
  • Telnet access uses the Command Line Interface (CLI) structure and syntax to completely configure and control the SA-82-AR. This Axess Ready (AR) device also supports the DxP protocol, which allows software developers to integrate the unit into custom applications.
  • Up to 2 systems can be continuously monitored with AutoPing, with automatic power control upon loss of contact. Reboot crashed systems, or provide auto power-up or - down for environmental controls and notification systems.
  • The SA-82-AR utilizes 2 levels of password security, with only the administrative account having access to setup and configuration.
  •  

    Physical

     

    Height

    1.8125”

    Width

    11.375”

    Depth

    7.625”

    Weight

    4.75 lb.

    Temperature

    5 - 35° C

    Humidity Range

    5% to 95% R.H., non-condensing

    AC

     

    Load Rating

    8 Amps @ 120 Volts

    Power Requirement (no load)

    10 Watts

    UL 1449-2 Adjunct Classification

    Test Results

    1000 surges, 6000 Volts, 3000 Amps,C1 pulse, measured

    suppressed voltage 290 Volts, no failures

    Maximum Applied Surge Pulse

    Joule Rating

    Unlimited, due to current limiting (8 x 20 µs)

    Maximum Applied Surge Pulse

    Voltage

    6000 volts (1.2 x 50 µs pulse),industry standard rating

    Maximum Applied Surge Pulse

    Current

    Unlimited, due to current limiting (8 x 20 µs)*

    Endurance

    IEEE C62.41-1991 Category B3 (C1)

    Pulses

    1 kV>500,000; 3 kV>10,000; 6 kV>1000

    Overvoltage Shutdown

    145 Volts (resume at 135 Volts)

    EMI/RFI

    Filter

    Normal Mode (50 Ω load)

    30 dB@100 kHz; 56 dB@300 kHz;64 dB@3 MHz;

    24 dB@30 MHz

    Common Mode (50 Ω

    load)

    9 dB@300 kHz; 16 dB@1 MHz;28 dB@5 MHz;

    35 dB@20 MHz

    Compliance

     

    UL/cUL

    UL60950 Listed I.T.E. File No. E225914

    Conforms to UL Stds 1283 & 1449

    CSA

    Certified to CSA Std C22.2 No. 8

    CE

    Directives 89/336/EEC, 92/31/EEC and 93/68/EEC EN 60950: 3rd Edition

    EN55022: 1998 Class B

    FCC

    Part 15 Class B

    Network

    Single 10/100 Unshielded Twisted Pair Ethernet Jack

    IP Addressed: DHCP Assigned or Static

    Internal HTTP Web Server

    Forms Processing Browser Required

    Internal Telnet Server

     

    California Proposition 65

    PVC-coated Products; PVC-coated Wires and Cables

    WARNING: This product can expose you to chemicals including DINP and/or DEHP, which are known to the state of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov or our information page: California Proposition 65.